Delta C2000 Series User Manual page 700

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

ID*
Display on LCM Keypad
44
Action level
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Incorrect setting of encoder
parameter
Pr. 01-00 is set too small
Incorrect setting for ASR
parameters and accel./decel. time
Incorrect setting for PG feedback
stall
ID*
Display on LCM Keypad
45
Action level
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Incorrect settings for PG feedback
parameters
Incorrect settings for ASR
parameters and accel./decel. time
Incorrect settings of encoder
parameters
Accel./Decel. time is too short
Incorrect settings of torque limit
parameters (Pr. 06-12, Pr.
11-17–20)
Motor shaft lock
Mechanical brake is not released
Fault Name
Under PG mode, when the motor frequency exceeds
the encoder observer stall level (Pr. 10-10) and starts to
PG feedback stall
count, the fault time is longer than the detection time of
(GF3)
encoder observer stall (Pr. 10-11), then PGF3 fault
occurs.
Action and Reset
Pr. 10-10
Pr. 10-11
Pr. 10-12
0: warn and keep operation
1: warn and ramp to stop
2: warn and coast to stop
Manual reset
Immediately reset
Yes
Reset encoder parameter (Pr. 10-01)
Set proper value for Pr. 01-00.
Reset ASR parameters.
Set correct accel./decel. time.
Reset proper values for Pr. 10-10 and Pr. 10-11
Fault Name
Under PG mode, when the motor frequency exceeds
PG slip error
encoder observer slip range (Pr. 10-13) and starts to
(PGF4)
count, the fault time is longer than the detection time of
encoder observer slip (Pr. 10-14), PGF4 fault occurs.
Action and Reset
Pr. 10-13
Pr. 10-14
Pr. 10-15
0: warn and keep operation
1: warn and ramp to stop
2: warn and coast to stop
When Pr. 10-15=0, PGF4 is a "Warning", when the deviation between
Auto
output frequency and motor frequency is smaller than the encoder
observer slip range, the warning is automatically cleared.
Manual When Pr. 10-15=1 or 2, PGF4 is a "Fault". You must reset manually.
Immediately reset
When Pr. 10-15=1 or 2, PGF4 is a "Fault", and the fault is recorded.
Reset correct values for Pr. 10-13 and Pr. 10-14.
Reset ASR parameters.
Set correct accel./decel time.
Reset encoder parameters (Pr. 10-01).
Reset proper accel./decel. time.
Reset proper setting values for Pr. 06-12 and Pr. 11-17–Pr. 17-20.
Remove causes of motor shaft lock.
Check the action sequence of the system.
14-29
Chapter 14 Fault Codes and DescriptionsC2000
Fault Descriptions
Corrective Actions
Fault Descriptions
Corrective Actions