Delta C2000 Series User Manual page 260

Vector control drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Environment
Noise immunity
Operation/ storage
Vibration/ shock immunity
8-11-4 Communication Parameters for VFD-C2000 Connected to Ethernet
When VFD-C2000 is linked to Ethernet, please set up the communication parameters
the table below. Ethernet master will be able to read/write the frequency word and control word of
VFD-C2000 after communication parameters setup.
Parameter
Pr. 00-20
Pr. 00-21
Pr. 09-30
Pr. 09-75
Pr. 09-76
Pr. 09-77
Pr. 09-78
Pr. 09-79
Pr. 09-80
Pr. 09-81
Pr. 09-82
Pr. 09-83
Pr. 09-84
Pr. 09-85
Pr. 09-86
Pr. 09-87
8-11-5
Basic Registers
BR#
R/W
#0
R
Model name
Firmware
#1
R
version
Release date of
#2
R
the version
#11
R/W
Modbus Timeout Pre-defined setting: 500 (ms)
#13
R/W
Keep Alive Time Pre-defined setting: 30 (s)
ESD (IEC 61800-5-1, IEC 61000-4-2)
EFT (IEC 61800-5-1, IEC 61000-4-4)
Surge Test (IEC 61800-5-1, IEC 61000-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 61000-4-6)
Operation: -10°C–50°C (temperature), 90% (humidity)
Storage: -25°C –70°C (temperature), 95% (humidity)
International standard: IEC 61800-5-1, IEC 60068-2-6/ IEC
61800-5-1, IEC 60068-2-27
Function
Source of frequency
command setting
Source of operation
command setting
Decoding method for
communication
IP setting
IP address -1
IP address -2
IP address -3
IP address -4
Netmask -1
Netmask -2
Netmask -3
Netmask -4
Default gateway -1
Default gateway -2
Default gateway -3
Default gateway -4
Content
Set up by the system; read only. The model code of
CMC-MOD01=H'0203
Displaying the current firmware version in hex, e.g. H'0100 indicates the
firmware version V1.00.
Displaying the data in decimal form. 10,000s digit and 1,000s digit are for
"month"; 100s digit and 10s digit are for "day".
For 1 digit: 0 = morning; 1 = afternoon.
Set value (Dec)
The frequency command is controlled by
8
communication card.
The operation command is controlled by
5
communication card.
0
Decoding method for Delta AC motor drive
0
Static IP(0) / Dynamic distribution IP(1)
192
IP address 192.168.1.5
168
IP address 192.168.1.5
1
IP address 192.168.1.5
5
IP address 192.168.1.5
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
0
Netmask 255.255.255.0
192
Default gateway 192.168.1.1
168
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
Explanation
8-27
Chapter 8 Option CardsC2000
based
Explanation
on

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents