4-1 System Wiring Diagram
Figure 4-1
Note: Please refer to Chapter 4-2 Wiring
Diagram for detailed wiring information.
Power input
Please refer to Chapter 9 Specification Table in
terminal
user manual for detail.
There may be a large inrush current during power
NFB or fuse
on. Refer to 7-2 NFB to select a suitable NFB or
7-3 Fuse Specification Chart.
Switching the power ON/OFF before the
Electromagnetic
magnetic contactor more than 1 x per hour can
contactor
cause damage to the drive.
When the mains power capacity is > 500kVA or
when the drive is preceded by a capacitor bank,
the instantaneous peaks voltages and current may
AC reactor
destroy the drive. In that case it is recommended
(input terminal)
to install an AC input reactor which will also
improve the power factor and harmonics. The
cable between reactor and drive should be < 10m.
Please refer to Chapter 7-4.
Used to reduce radiated emission, especially in
environments with audio devices, and reduce
Zero-phase
input and output side interference.
reactor
The effective range is AM band to 10MHz.
Please refer to Chapter 7-5.
Can be used to reduce electromagnetic
EMC filter
interference.
Please refer to Chapter 7-6.
Brake module &
Used to shorten the deceleration time of the
Brake resistor
motor.
(BR)
Please refer to Chapter 7-1.
The wiring length of the motor will affect switching
AC reactor
current peaks. It is recommended to install an AC
(output
output reactor when the motor wiring length
terminal)
exceeds the value listed in Chapter 7-4.
4-3
Chapter 4 WiringC2000
T
a
Table 4-1