Chapter 12 Description of Parameter SettingsC2000
Analog Output 1 in REV Direction (AFM1)
Analog Output 2 in REV Direction (AFM2)
Settings
AFM2 Output Bias
Settings
Example 1, AFM2 0–10V is set to the output frequency, the output equation is:
10V * (output frequency / Pr. 01-00) * Pr. 03-24 + 10V * Pr. 03-27
Example 2, AFM2 0–20mA is set to the output frequency, the output equation is:
20mA * (output frequency / Pr. 01-00) * Pr. 03-24 + 20mA * Pr. 03-27
Example 3, AFM2 4–20mA is set to the output frequency, the output equation is:
4mA + 16mA * (output frequency / Pr. 01-00) * Pr. 03-24 + 16mA * Pr. 03-27
This parameter sets the corresponding voltage for the analog output 0.
AVI Terminal Input Selection
Settings
ACI Terminal Input Selection
Settings
When you change the input mode, verify that the external terminal switch (SW3, SW4)
corresponds to the setting for Pr. 03-28–Pr. 03-29.
0: Absolute value of output voltage
1: Reverse output 0 V; forward output 0–10 V
2: Reverse output 5–0 V; forward output 5–10 V
-100.00–100.00 %
0: 0–10V
1: 0–20mA
2: 4–20mA
0: 4–20mA
1: 0–10V
2: 0–20mA
12.1-03-19
Default: 0
Default: 0
Default: 0.00
Default: 0
Default: 0