Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT2)
Settings
Over-torque Detection Time (OT2)
Settings
 When the output current exceeds the over-torque detection level (Pr. 06-07 or Pr. 06-10) and
exceeds the over-torque detection time (Pr. 06-08 or Pr. 06-11), the over-torque detection follows
the setting of Pr. 06-06 and Pr. 06-09.
When you set Pr. 06-06 or Pr. 06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps
running. The warning remains on until the output current is smaller than 5% of the over-torque
detection level.
 When you set Pr. 06-06 or Pr. 06-09 to 2 or 4, an ot1 / ot2 warning displays and the drive stops
running after over-torque detection. The drive keeps running after you manually reset it.
10–250% (100% corresponds to the rated current of the drive)
0.0–60.0 sec.
10–250% (100% corresponds to the rated current of the drive)
0.0–60.0 sec.
12.1-06-6
Chapter 12 Description of Parameter SettingsC2000
Default: 120
Default: 0.1
Default: 120
Default: 0.1