Chapter 12 Description of Parameter SettingsC2000
Settings
Functions
Count value reached,
18
returns to 0 (Pr. 02-19)
External interrupt B.B.
19
input (Base Block)
20
Warning Output
21
Over-voltage
Over-current Stall
22
Prevention
Over-voltage Stall
23
prevention
24
Operation Mode
25
Forward Command
26
Reverse Command
Output when Current ≥
27
Pr. 02-33
Output when Current <
28
Pr. 02-33
Output when frequency
29
≥ Pr. 02-34
Output when Frequency
30
< Pr. 02-34
Y-connection for the
31
Motor Coil
-connection for the
32
Motor Coil
Zero Speed (actual
33
output frequency)
Zero speed including
34
stop (actual output
frequency)
Error Output Selection 1
35
(Pr. 06-23)
Error Output Selection 2
36
(Pr. 06-24)
Error Output Selection 3
37
(Pr. 06-25)
Error Output Selection 4
38
(Pr. 06-26)
Position reached
39
(Pr. 10-19)
Speed reached
40
(including speed)
When the drive executes the external counter, this contact is
active if the count value is equal to the setting value for Pr.02-19.
Active when external interrupt (B.B.) stop output occurs in the
drive.
Active when the warning is detected.
Active when the over-voltage is detected.
Active when the over-current stall prevention is detected.
Active when the over-voltage stall prevention is detected.
Active when the operation command is controlled by external
terminal. (Pr. 00-21≠0)
Active when the operation direction is forward.
Active when the operation direction is reverse.
Active when current is ≥ Pr. 02-33.
Active when current is < Pr. 02-33
Active when frequency is ≥ Pr. 02-34.
Active when frequency is < Pr. 02-34.
Active when Pr. 05-24=1, when frequency output is lower than Pr.
05-23 minus 2Hz, and lasts longer than Pr. 05-25.
Active when Pr. 05-24=1, when frequency output is higher than Pr.
05-23 plus 2Hz, and lasts longer than Pr. 05-25.
Active when the actual output frequency is 0. (the drive is in RUN
mode)
Active when the actual output frequency is 0 or stopped.
Active when Pr. 06-23 is ON.
Active when Pr. 06-24 is ON.
Active when Pr. 06-25 is ON.
Active when Pr. 06-26 is ON.
Active when the PG position control point reaches Pr. 10-19.
Active when the output frequency reaches frequency setting or
stop.
12.1-02-14
Descriptions