Ac/Dc Reactors - Delta VFD300C43S-HS User Manual

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 7 Optional AccessoriesC2000-HS
7-4 AC/DC Reactor
AC Input Reactor
Installing an AC reactor in the input side of an AC motor drive can increase
power factor, reduce input current, increase system capacity and reduce interference generated from
motor drive. It also reduces momentary voltage surges or abnormal current spikes. For example, when the
main power capacity is higher than 500 kVA, or when using a switching capacitor bank, momentary voltage
and current spike may damage the AC motor drive's internal circuit. An
AC motor drive protects it by suppressing surges.
Installation
Install an AC input reactor in series with the main power to the three input phases R/ S/ T as shown
below:
Following table shows the standard AC reactors specification of Delta C2000-HS
380V–460V / 50–60Hz
Model
HP
VFD300C43S-HS 40
VFD370C43S-HS 50
VFD750C43A-HS 100
VFD1100C43A-HS 150
VFD1600C43A-HS 215
VFD2200C43A-HS 300
VFD3550C43A-HS 475
Wiring of AC input reactor
Rated Current
Saturation current
(Arms)
(Arms)
60
102.6
73
124.2
150
257.4
220
376.2
310
531
460
786.6
683
1168.2
AC reactor on the input side of the
3%
5%
impedance
impedance
(mH)
(mH)
0.405
0.675
0.334
0.555
0.162
0.270
0.110
0.184
0.078
0.131
0.054
0.090
0.036
0.060
7-6
line impedance, improve
Figure 7-5
3%
Built-in
Input AC reactor
DC reactor
Delta part #
Yes
DR060AP405
Yes
DR073AP334
Yes
DR150AP162
Yes
DR220AP110
Yes
DR310AP078
Yes
DR460AP054
Yes
DR683AP036
Table 7-5

Hide quick links: