  • Page 2 Chapter 1 Introduction The AC motor drive should be kept in the shipping carton or crate before installation. In order to retain the warranty coverage, the AC motor drive should be stored properly when it is not to be used for an extended period of time.
  • Page 3: Receiving And Inspection

    Chapter 1 Introduction| 1.1 Receiving and Inspection This VFD-E AC motor drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC motor drive, please check for the following: Check to make sure that the package includes an AC motor drive, the User Manual/Quick Start and CD.
  • Page 4: Series Number Explanation

    Chapter 1 Introduction| 1.1.3 Series Number Explanation 007E23A 1230 Pro du ction n um ber Pro du ction w eek Pro du ction year 2008 Pro du ction f act ory T: Taoyu an, W: Wu jian g 230V 3- ph ase 1HP (0.75kW ) Mo del If the nameplate information does not correspond to your purchase order or if there are any problems, please contact your distributor.
  • Page 5 Chapter 1 Introduction| 1-5HP/0.75-3.7kW (Frame B) Input terminals (R/L1, S/L2, T/L3) Keypad cover Case body Control board cover Output terminals (U/T1, V/T2, W/T3) 7.5-15HP/5.5-11kW (Frame C) Input terminals (R/L1, S/L2, T/L3) Case body Keypad cover Control board cover Output terminals (U/T1, V/T2, W/T3) 20-30HP/15-22kW (Frame D) Input terminals...
  • Page 6 Chapter 1 Introduction| Internal Structure READY: power indicator RUN: status indicator FAULT: fault indicator Switch to ON for 50Hz, refer to P 01.00 to P01.02 for details Switch to ON for free run to stop refer to P02.02 Switch to ON for setting frequency source to ACI (P 02.00=2) ACI terminal (ACI/AVI2 switch ) NPN/PNP...
  • Page 7 Chapter 1 Introduction| Frame B: above the nameplate Frame C: above the warning label Frame D: near the input terminals (R/L1, S/L2, T/L3) Frame Power range Models VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A, VFD015E23A/43A VFD002E11C/21C/23C, VFD004E11C/21C/23C/43C, A (A1) 0.25-2hp (0.2-1.5kW) VFD007E21C/23C/43C, VFD015E23C/43C VFD002E11T/21T/23T, VFD004E11T/21T/23T/43T, VFD007E21T/23T/43T, VFD015E23T/43T VFD002E11P/21P/23P, VFD004E11P/21P/23P/43P, A (A2)
  • Page 8: Remove Instructions

    Chapter 1 Introduction| RFI Jumper RFI Jumper: The AC motor drive may emit the electrical noise. The RFI jumper is used to suppress the interference (Radio Frequency Interference) on the power line. Main power isolated from earth: If the AC motor drive is supplied from an isolated power (IT power), the RFI jumper must be cut off. Then the RFI capacities (filter capacitors) will be disconnected from ground to prevent circuit damage (according to IEC 61800-3) and reduce earth leakage current.
  • Page 9 Chapter 1 Introduction| Remove Keypad Remove Front Cover Press and hold in the tabs on each side of the cover. Pull the cover up to release. Step 1 Step 2 Remove RST Terminal Cover Remove UVW Terminal Cover For Frame B, Frame C and Frame D: it only For Frame B, Frame C and Frame D: it only needs to turn the cover lightly to open it needs to turn the cover light to open the cover...
  • Page 10 Chapter 1 Introduction| 1.2 Preparation for Installation and Wiring 1.2.1 Ambient Conditions Install the AC motor drive in an environment with the following conditions: -10 ~ +50°C (14 ~ 122°F) for UL & cUL Air Temperature: -10 ~ +40°C (14 ~ 104°F) for side-by-side mounting Relative Humidity: <90%, no condensation allowed Atmosphere...
  • Page 11 Frame B, C and D Mounting Clearances Single drive Side-by-side installation Air flow 150mm 150mm Air Flow 150mm 150mm For VFD-E-P series: heat sink system example Air-extracting apparatus User 's heat sink should comply with following conditions: Control panel Duct temperature Air flow speed 2m/sec 1.
  • Page 12 Chapter 1 Introduction| When AC motor drive is installed in a confined space (e.g. cabinet), the surrounding temperature must be within 10 ~ 40°C with good ventilation. DO NOT install the AC motor drive in a space with bad ventilation. Prevent fiber particles, scraps of paper, saw dust, metal particles, etc.
  • Page 13 Chapter 1 Introduction| 1.2.2 DC-bus Sharing: Connecting the DC-bus of the AC Motor Drives in Parallel This function is not for VFD-E-T series. The AC motor drives can absorb mutual voltage that generated to DC bus when deceleration. Enhance brake function and stabilize the voltage of the DC bus.
  • Page 14 Chapter 1 Introduction| 1.3 Dimensions (Dimensions are in millimeter and [inch]) Frame A Unit: mm [inch] Frame 72.0 60.0 142.0 120.0 152.0 50.0 A (A1) [2.83] [2.36] [5.59] [4.72] [5.98] [1.97] [0.18] [0.20] [0.20] 72.0 56.0 155.0 143.0 111.5 A (A2) [2.83] [2.20] [6.10]...
  • Page 15 Chapter 1 Introduction| Frame B Unit: mm [inch] Frame 100.0 89.0 174.0 162.0 152.0 50.0 [3.94] [3.50] [6.86] [6.38] [5.98] [1.97] [0.16] [0.22] [0.22] NOTE Frame B (B1): VFD007E11A, VFD015E21A, VFD022E21A/23A/43A, VFD037E23A/43A, VFD007E11C, VFD015E21C, VFD022E21C/23C/43C, VFD037E23C/43C 1-14 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14...
  • Page 16 Chapter 1 Introduction| Frame C Unit: mm [inch] Frame 130.0 116.0 260.0 246.5 169.2 78.5 [5.12] [4.57] [10.24] [9.70] [6.66] [3.09] [0.31] [0.26] [0.22] NOTE Frame C (C1): VFD055E23A/43A, VFD075E23A/43A, VFD110E23A/43A, VFD055E23C/43C, VFD075E23C/43C, VFD110E23C/43C Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 1-15...