Monitored Data; Technical Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Table 446:
87LOZREF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
CT connection type
1=Type 1
2=Type 2
Table 447:
87LOZREF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.3.3.8
4.3.3.9
615 series ANSI
Technical Manual
Unit
Step
Unit
Step
ms
1

Monitored data

Table 448:
87LOZREF Monitored data
Name
Type
PICKUP_DUR
FLOAT32
RES2H
BOOLEAN
IDIFF
FLOAT32
IBIAS
FLOAT32
87LOZREF
Enum

Technical data

Table 449:
87LOZREF Technical data
Characteristic
Operation accuracy
1)2)
Pickup time
I
Fault
value
Reset time
Reset ratio
Table continues on next page
Default
Description
1=enable
Operation Disable / Enable
2=Type 2
CT connection type
Default
Description
20
Reset delay time
Values (Range)
Unit
0.00...100.00
%
0=False
1=True
0.00...80.00
xIn
0.00...80.00
xIn
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2.5% of the set value or ±0.002 x I
Minimum
Trip
= 2.0 × set
37 ms
Typically 40 ms
Typically 0.96
Section 4
Protection functions
Description
Ratio of pickup time / trip time
2nd harmonic restraint
Differential current
Stabilization current
Status
±2 Hz
n
n
Typical
Maximum
41 ms
45 ms
549