ABB 615 series Technical Manual page 855

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
615 series ANSI
Technical Manual
Open CT circuits create extremely high voltages in the circuits, which
may damage the insulation and cause further problems. This must be
taken into consideration especially when the protection functions are
blocked.
When the reference current is not connected to the protection relay, the
function should be turned off. Otherwise, the FAIL output is activated
when unbalance occurs in the phase currents even if there was nothing
wrong with the measurement circuit.
Reference current measured with core-balanced current transformer
CCM compares the sum of phase currents to the current measured with the core-balanced
CT.
IL1
IL2
IL3
GUID-DA7A48EF-0F07-4665-9A09-87188E5A9982 V2 EN
Figure 437:
Connection diagram for reference current measurement with core-
balanced current transformer
Supervision functions
protection relay
CCM
I_A
I_A
FAIL
I_B
I_B
ALARM
I_C
I_C
I_REF
I_REF
BLOCK
Section 6
849