Section 8
Measurement functions
900
When the frequency measurement function f is unable to measure the
network frequency in the undervoltage situation, the measured values are
set to the nominal and also the quality information of the data set
accordingly. The undervoltage limit is fixed to 10 percent of the nominal
for the frequency measurement.
Limit value supervision
The limit value supervision function indicates whether the measured value of X_INST
exceeds or falls below the set limits. The measured value has the corresponding range
information X_RANGE and has a value in the range of 0 to 4:
0: "normal"
1: "high"
2: "low"
3: "high-high"
4: "low-low"
The range information changes and the new values are reported.
GUID-AAAA7367-377C-4743-A2D0-8DD4941C585D V1 EN
Figure 466:
Presentation of operating limits
The range information can also be decoded into boolean output signals on some of the
measuring functions and the number of phases required to exceed or undershoot the limit
before activating the outputs and can be set with the Num of phases setting in the three-
phase measurement functions IA, IB, IC and VA, VB, VC. The limit supervision boolean
alarm and warning outputs can be blocked.
1MAC059074-MB A
615 series ANSI
Technical Manual