Section 4
Protection functions
512
value basically allows the no-load current of the power transformer and small
inaccuracies of the current transformers, but it can also be used to influence the
overall level of the operating characteristic. At the rated current, the no-load losses of
the power transformer are about 0.2 percent. If the supply voltage of the power
transformer suddenly increases due to operational disturbances, the magnetizing
current of the transformer increases as well. In general the magnetic flux density of
the transformer is rather high at rated voltage and a rise in voltage by a few percent
causes the magnetizing current to increase by tens of percent. This should be
considered in Low trip value
In section 2, where End section 1 < Ib/In < End section 2, is called the influence area
of Slope section 2. In this section, variations in the starting ratio affect the slope of the
characteristic, that is, how big a change in the differential current is required for
tripping in comparison with the change in the load current. The starting ratio should
consider CT errors and variations in the transformer tap changer position (if not
compensated). Too high a starting ratio should be avoided, because the sensitivity of
the protection for detecting inter-turn faults depends basically on the starting ratio.
In section 3, where Ib/In > End section 2, the slope of the characteristic can be set by
Slope section 3 that defines the increase in the differential current to the
corresponding increase in the biasing current.
Low trip
Curve
value
I
[%I
]
d
r
1
50 %Ir
2
20 %Ir
300
3
5 %Ir
200
100
100
GUID-739E1789-778D-44BF-BD4A-6BD684BF041D-ANSI V1 EN
Figure 254:
Setting range for biased low stage
If the biasing current is small compared to the differential current of the phase angle
between the winding 1 and winding 2 phase currents is close to zero (in a normal situation,
Slope
End
section
section
2
2
50 %
100 %Ir
30 %
150 %Ir
10 %
500 %Ir
Curve 1
Curve 2 ( Default settigs )
Curve 3
200
300
1MAC059074-MB A
400
500
I
[%I
d
615 series ANSI
Technical Manual
]