ABB 615 series Technical Manual page 628

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
622
GUID-EE729648-3D09-4EBE-B662-80E59DA7C0A4-ANSI V2 EN
Figure 312:
Behavior of different IDMT reset modes. Operate signal is based on
settings Type of reset curve = "Def time reset" and Type of time reset=
"Freeze Op timer". The effect of other reset modes is also presented
The Time multiplier setting is used for scaling the IDMT trip times.
The Minimum trip time setting parameter defines the minimum desired trip time for
IDMT. The setting is applicable only when the IDMT curves are used.
The Minimum trip time setting should be used with care because the
operation time is according to the IDMT curve, but always at least the
value of the Minimum trip time setting. For more information, see the
IDMT curves for overcurrent protection
1MAC059074-MB A
section in this manual.
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents