Signals

Table 76:
GOOSERCV_INT32 Output signals
Name
Type
OUT
INT32
VALID
BOOLEAN

Type conversion function blocks

QTY_GOOD function block

Function block

GUID-1999D6D9-4517-4FFE-A14D-08FDB5E8B9F6 V1 EN
Figure 54:
Function block

Functionality

The QTY_GOOD function block evaluates the quality bits of the input signal and passes
it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (logic function output,
binary input, application function output or received GOOSE signal). Due to application
logic quality bit propagation, each (simple and even combined) signal has quality which
can be evaluated.
The OUT output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.