Signals; Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.1.7.6
4.1.7.7
Table 295:
37M Group settings (Basic)
Parameter
Values (Range)
Pickup value low
0.01...0.50
Pickup value high
0.01...1.00
Trip delay time
400...600000
615 series ANSI
Technical Manual
is either disconnected from the load or the coupling mechanism is faulty. If the motor is
allowed to run in this condition, it may aggravate the fault in the coupling mechanism or
harm the personnel handling the machine. Therefore, the motor has to be disconnected
from the power supply as soon as the above condition is detected.
37M detects the condition by monitoring the current values and helps disconnect the
motor from the power supply instantaneously or after a delay according to the
requirement.
When the motor is at standstill, the current will be zero and it is not recommended to
activate the trip during this time. The minimum current drawn by the motor when it is
connected to the power supply is the no load current, that is, the higher pickup value
current. If the current drawn is below the lower pickup value current, the motor is
disconnected from the power supply. 37M detects this condition and interprets that the
motor is de-energized and disables the function to prevent unnecessary trip events.

Signals

Table 293:
37M Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
BLOCK
BOOLEAN
Table 294:
37M Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
xIn
0.01
xIn
0.01
ms
10
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block all binary outputs by resetting timers
Description
Trip
Pickup
Default
Description
0.10
Current setting/Pickup value low
0.50
Current setting/Pickup value high
2000
Trip delay time
Section 4
Protection functions
291