615 series ANSI
Technical Manual
Characteristic
Reset time
Trip time accuracy
Suppression of harmonics
1) VG = 1.0 × Vn
2) Includes the delay of the signal output contact, results based on statistical distribution of 1000
measurements
Technical revision history
Table 387:
21YN Technical revision history
Technical revision
B
C
D
E
Harmonics-based ground-fault protection 51NHA
Identification
Description
Harmonics-based ground-fault
protection
Function block
51NHA
PICKUP
IG
TRIP
I_REF_RES
BLOCK
GUID-9A831169-A6A0-4689-9715-A61794979C12 V1 EN
Figure 192:
Function block
Functionality
The harmonics-based ground-fault protection function 51NHA is used instead of a
traditional ground-fault protection in networks where a fundamental frequency
component of the bround-fault current is low due to compensation.
Value
40 ms
±1.0% of the set value of ±20 ms
-50 dB at f = n × f
Change
Internal improvement.
Voltage pickup value setting range and default value
change.
Internal improvement.
Internal improvement.
IEC 61850
IEC 60617
identification
identification
HAEFPTOC
Io>HA
Section 4
Protection functions
, where n = 2, 3, 4, 5,...
n
ANSI/IEEE C37.2
device number
51NHA