Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Table 625:
32U Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 626:
32U Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
Reset delay time
0...60000
Pol reversal
0=False
1=True
Disable time
0...60000
4.8.1.8
615 series ANSI
Technical Manual
Unit
Step
Unit
Step
ms
10
ms
1000

Monitored data

Table 627:
32U Monitored data
Name
Type
PICKUP_DUR
FLOAT32
P
FLOAT32
Q
FLOAT32
S
FLOAT32
PF_ANGLE
FLOAT32
32U
Enum
Default
Description
1=enable
Operation Disable / Enable
Default
Description
3=Pos Seq
Selection of power calculation method
20
Reset delay time
0=False
Reverse the definition of the power direction
0
Additional wait time after CB closing
Values (Range)
Unit
0.00...100.00
%
-160.000...160.0
xSn
00
-160.000...160.0
xSn
00
0.000...160.000
xSn
-180.00...180.00
deg
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
Ratio of pickup time / trip time
Active power
Reactive power
Apparent power
Power factor angle
Status
723

Advertisement

Table of Contents
loading

Table of Contents