Section 3
Basic functions
3.17.11.4
192
Description setting can be used for storing information on the actual use of the control
point in application, for instance.
For example, if the Operation mode is "Toggle", the output O# is initially "False". The
rising edge in IN# sets O# to "True". The falling edge of IN# has no effect. Next rising
edge of IN# sets O# to "False".
GUID-F0078144-A40B-4A72-915A-0E6665F8DEB1 V1 EN
Figure 98:
Operation in "Toggle" mode
The BLOCK input can be used for blocking the functionality of the outputs. The operation
of the BLOCK input depends on the Operation mode setting. If Operation mode is
"Toggle", the output state freezes and cannot be changed while the BLOCK input is active.
If Operation mode is "Pulsed", the activation of the BLOCK input resets the outputs to the
"False" state and further control requests are ignored while the BLOCK input is active.
From the remote communication point of view SPC toggled operation
mode is always working as persistent mode. The output O# follows the
value written to the input IN#.

Signals

Table 189:
SPC Input signals
Name
Type
BLOCK
BOOLEAN
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
Table continues on next page
Default
Description
0=False
Block signal for activating the blocking mode
0=False
Input of control point 1
0=False
Input of control point 2
0=False
Input of control point 3
0=False
Input of control point 4
0=False
Input of control point 5
0=False
Input of control point 6
0=False
Input of control point 7
0=False
Input of control point 8
1MAC059074-MB A
615 series ANSI
Technical Manual