Section 4
Protection functions
4.8.1.6
4.8.1.7
Table 624:
32U Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.01...2.00
Trip delay time
40...300000
722
errors. The manufacturer of the measuring devices is to be contacted for
information on the measuring errors.
If the measuring errors are not compensated for, the underpower setting
should not be lower than the sum of the current-measuring and voltage-
measuring errors.
For example, if the error of the current-measuring device is 2% and that of
the voltage-measuring device is 1%, the minimum setting is (2 + 1)% =
3%.

Signals

Table 622:
32U Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I1
SIGNAL
V_A
SIGNAL
V_B
SIGNAL
V_C
SIGNAL
V1
SIGNAL
BLOCK
BOOLEAN
DISABLE
BOOLEAN
Table 623:
32U Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
xSn
0.01
ms
10
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Positive sequence current
0
Phase-to-ground voltage A or phase-to-phase voltage
AB
0
Phase-to-ground voltage B or phase-to-phase voltage
BC
0
Phase-to-ground voltage C or phase-to-phase voltage
CA
0
Positive phase sequence voltage
0=False
Block signal for activating the blocking mode
0=False
Signal to block the function during generator startup
Description
Trip
Pickup
Default
Description
0.10
Pickup value
40
Trip delay time
1MAC059074-MB A
615 series ANSI
Technical Manual