Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Table 474:
87G, 87M Group settings (Advanced)
Parameter
Values (Range)
Slope section 3
10...100
DC restrain enable
0=False
1=True
Table 475:
87G, 87M Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
CT connection type
1=Type 1
2=Type 2
CT ratio Cor Line
0.40...4.00
CT ratio Cor Neut
0.40...4.00
4.3.5.8
615 series ANSI
Technical Manual
Unit
Step
%
1
Unit
Step
0.01
0.01

Monitored data

Table 476:
87G, 87M Monitored data
Name
Type
OPR_A
BOOLEAN
OPR_B
BOOLEAN
OPR_C
BOOLEAN
INT_BLKD_A
BOOLEAN
INT_BLKD_B
BOOLEAN
INT_BLKD_C
BOOLEAN
ID_A
FLOAT32
ID_B
FLOAT32
ID_C
FLOAT32
IB_A
FLOAT32
IB_B
FLOAT32
IB_C
FLOAT32
I_ANGL_A1_B1
FLOAT32
Table continues on next page
Default
Description
100
Slope of the third line of the operating
characteristics
0=False
Setting for enabling DC restrain feature
Default
Description
1=enable
Operation Disable / Enable
1=Type 1
CT connection type. Determined by the
directions of the connected current
transformers
1.00
CT ratio correction, line side
1.00
CT ratio correction, neutral side
Values (Range)
Unit
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0.00...80.00
xIr
0.00...80.00
xIr
0.00...80.00
xIr
0.00...80.00
xIr
0.00...80.00
xIr
0.00...80.00
xIr
-180.00...180.00
deg
Section 4
Protection functions
Description
Trip phase A
Trip phase B
Trip phase C
Internal block status phase A
Internal block status phase B
Internal block status phase C
Differential current phase A
Differential current phase B
Differential current phase C
Biasing current phase A
Biasing current phase B
Biasing current phase C
Current phase angle phase A
to B, line side
585

Advertisement

Table of Contents
loading

Table of Contents