Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
8.1.4.3
8.1.4.4
Table 796:
IA,IB,IC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
A high high limit
0.00...40.00
A high limit
0.00...40.00
A low limit
0.00...40.00
A low low limit
0.00...40.00
A deadband
100...100000
Table 797:
IA,IB,IC Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
1=RMS
2=DFT
615 series ANSI
Technical Manual

Signals

Table 794:
IA,IB,IC Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
BLOCK
BOOLEAN
Table 795:
IA,IB,IC Output signals
Name
Type
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
Settings
Unit
Step
xIn
1
xIn
1
xIn
1
xIn
1
1
Unit
Step
Measurement functions
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block signal for all binary outputs
Description
High alarm
High warning
Low warning
Low alarm
Default
Description
1=enable
Operation Disable / Enable
1=1 out of 3
Number of phases required by limit supervision
1.40
High alarm current limit
1.20
High warning current limit
0.00
Low warning current limit
0.00
Low alarm current limit
2500
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Default
Description
2=DFT
Selects used measurement mode
Section 8
907

Advertisement

Table of Contents
loading

Table of Contents