ABB 615 series Technical Manual page 584

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
578
The parameter r is the maximum remanence flux density in the CT core in pu from the
saturation flux density. The value of the parameter r depends on the magnetic material
used and also on the construction of the CT. For instance, if the value r = 0.4, the
remanence flux density can be 40 percent of the saturation flux density. The manufacturer
of the CT has to be contacted when an accurate value for the parameter r is needed. The
value r = 0.4 is recommended to be used when an accurate value is not available.
The required minimum time-to-saturate T
(10 ms when f
= 50 Hz).
n
Two typical cases are considered for the determination of the sufficient actual accuracy
limit factor F
:
a
1.
A fault occurring at the substation bus.
The protection must be stable at a fault arising during a normal operating situation.
The reenergizing of the transformer against a bus fault leads to very high fault
currents and thermal stress. Therefore, reenergizing is not preferred in this case. The
remanence can be neglected.
The maximum through-going fault current Ik
short circuit fault close to the supply transformer, the DC time constant T
current is almost the same as that of the transformer, the typical value being 100 ms.
Ik
= 6 I
max
R
T
= 100 ms
dc
ω
= 100π Hz
T
= 10 ms
m
K
= 1
r
Equation 114
with these values gives the result:
F
K
Ik
(
T
>
×
×
max
a
r
dc
GUID-C510CA46-3857-40D3-B40A-3C237BCE6E79 V2 EN
2.
Reenergizing against a fault occurring further down in the network.
The protection must be stable also during reenergization against a fault on the line. In
this case, the existence of remanence is very probable. It is assumed to be 40 percent
here.
On the other hand, the fault current is now smaller and since the ratio of the resistance
and reactance is greater in this location, having a full DC offset is not possible.
in 87G, 87M is half-fundamental cycle period
m
max
T
m
T dc
(
1
e
)
1
)
24
ω
× ×
+
1MAC059074-MB A
is typically 6 I
for a motor. At a
R
of the fault
dc
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents