Qty_Goose_Comm Function Block; Function Block; Functionality; Signals - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
3.16.3
3.16.3.1
3.16.3.2
3.16.3.3
615 series ANSI
Technical Manual

QTY_GOOSE_COMM function block

Function block

GUID-0FDC082E-C9A8-4B02-9878-6C49E44B7C0E V1 EN
Figure 56:
Function block

Functionality

The QTY_GOOSE_COMM function block evaluates the peer device communication
status from the quality bits of the input signal and passes it as a Boolean signal to the
application.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the communication status of the GOOSE function block. When
the output is in the true (1) state, the GOOSE communication is active. The value false (0)
indicates communication timeout.

Signals

Table 81:
QTY_GOOSE_COMM Input signals
Name
Type
IN
Any
Table 82:
QTY_GOOSE_COMM Output signals
Name
COMMVALID
Default
0
Type
BOOLEAN
Section 3
Basic functions
Description
Input signal
Description
Output signal
143