to primary peak value units when the protection relay converts the recordings to the
COMTRADE format.
COMTRADE is the general standard format used in storing disturbance
recordings.
The binary channels are sampled once per task execution of the disturbance recorder. The
task execution interval for the disturbance recorder is the same as for the protection
functions. During the COMTRADE conversion, the digital status values are repeated so
that the sampling frequencies of the analog and binary channels correspond to each other.
This is required by the COMTRADE standard.
The disturbance recorder follows the 1999 version of the COMTRADE
standard and uses the binary data file format.

Settings

Table 849:
DFR Non-group general settings
Parameter
Values (Range)
Operation
1=Enable
5=Disable
Record length
10...500
Pre-trg length
0...100
Operation
1=Saturation
mode
2=Overwrite
Exclusion time
0...1 000 000
Storage rate
32, 16, 8
Table continues on next page
Unit
Step
1
fundamental
1
cycles
%
1
1
ms
1
samples per
fundamental
cycle
Section 8
Measurement functions
Default
Description
1=Enable
DFR Enabled /
Disabled
50
Size of the
recording in
fundamental
cycles
50
Length of the
recording
preceding the
triggering
1
Operation
mode of the
recorder
0
The time during
which
triggerings of
same type are
ignored
32
Storage rate of
the waveform
recording
945

Advertisement

Table of Contents
loading

Table of Contents