Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.3.7
Table 261:
51V Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.05...5.00
Pickup value low
0.05...1.00
Voltage high limit
0.01...1.00
Voltage low limit
0.01...1.00
Pickup value mult
0.8...10.0
Time multiplier
0.05...15.00
Operating curve type
1=ANSI Ext Inv
2=ANSI Very Inv
3=ANSI Norm Inv
4=ANSI Mod Inv
5=ANSI DT
6=LT Ext Inv
7=LT Very Inv
8=LT Inv
9=IEC Norm Inv
10=IEC Very Inv
11=IEC Inv
12=IEC Ext Inv
13=IEC ST Inv
14=IEC LT Inv
15=IEC DT
17=Programmable
18=RI Type
19=RD Type
Trip delay time
40...200000
Table 262:
51V Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Table 263:
51V Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Curve parameter A
0.0086...120.0000
Table continues on next page
266

Settings

Unit
Step
xIn
0.01
xIn
0.01
xUn
0.01
xUn
0.01
0.1
0.01
ms
10
Unit
Step
Unit
Step
1
Default
Description
0.05
Pickup value
0.05
Lower pickup value based on voltage control
1.00
Voltage high limit for voltage control
1.00
Voltage low limit for voltage control
1.0
Multiplier for scaling the pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
15=IEC DT
Selection of time delay curve type
40
Trip delay time
Default
Description
1=Immediate
Selection of reset curve type
Default
Description
1=enable
Operation Disable / Enable
1=1 out of 3
Number of phases required for trip activation
28.2000
Parameter A for customer programmable
curve
1MAC059074-MB A
615 series ANSI
Technical Manual