Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 9
Control functions
Table 899:
25 Non group settings (Advanced)
Parameter
Values (Range)
Control mode
1=Continuous
2=Command
Close pulse
200...60000
Phase shift
-180...180
Minimum Syn time
0...60000
Maximum Syn time
100...6000000
Energizing time
100...60000
Closing time of CB
40...250
Voltage source switch
0=False
1=True
9.3.8
990
Unit
Step
ms
10
deg
1
ms
10
ms
10
ms
10
ms
10

Monitored data

Table 900:
25 Monitored data
Name
Type
ENERG_STATE
Enum
U_DIFF_MEAS
FLOAT32
FR_DIFF_MEAS
FLOAT32
PH_DIFF_MEAS
FLOAT32
U_DIFF_SYNC
BOOLEAN
PH_DIF_SYNC
BOOLEAN
FR_DIFF_SYNC
BOOLEAN
25
Enum
Default
Description
1=Continuous
Selection of synchro check command or
Continuous control mode
200
Breaker closing pulse duration
0
Correction of phase difference between
measured U_BUS and U_LINE
0
Minimum time to accept synchronizing
2000
Maximum time to accept synchronizing
100
Time delay for energizing check
60
Closing time of the breaker
0=False
Voltage source switch
Values (Range)
Unit
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
0.00...1.00
xUn
0.000...0.100
xFn
0.00...180.00
deg
0=False
1=True
0=False
1=True
0=False
1=True
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC059074-MB A
Description
Energization state of Line and
Bus
Calculated voltage amplitude
difference
Calculated voltage frequency
difference
Calculated voltage phase
angle difference
Voltage difference out of limit
for synchronizing
Phase angle difference out of
limit for synchronizing
Frequency difference out of
limit for synchronizing
Status
615 series ANSI
Technical Manual