Functionality

The GOOSERCV_INT8 function is used to connect the GOOSE 8 bit integer inputs to the
application.

Signals

Table 72:
GOOSERCV_INT8 Output signals
Name
Type
OUT
INT8
VALID
BOOLEAN

GOOSERCV_INTL function block

Function block

GUID-241A36E0-1BB9-4323-989F-39668A7B1DAC V1 EN
Figure 50:
Function block
Functionality
The GOOSERCV_INTL function is used to connect the GOOSE double binary input to
the application and extracting single binary position signals from the double binary
position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate state.
The default value (0) is used if VALID output indicates invalid status.
1MAC059074-MB A
Description
Output signal
Output signal
615 series ANSI
Technical Manual