Technical Revision History - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
9.1.9
9.2
9.2.1
615 series ANSI
Technical Manual

Technical revision history

Table 878:
52 Technical revision history
Technical revision
B
C
D
Table 879:
29DS Technical revision history
Technical revision
B
C
Table 880:
29GS Technical revision history
Technical revision
B
C
Disconnector position indication 52-TOC, 29DS and
Grounding switch indication 29GS
Identification
Function description
Disconnector position indication
Grounding switch indication
Change
Interlocking bypass input (ITL_BYPASS) and
opening enabled (OPEN_ENAD)/closing enabled
(CLOSE_ENAD) outputs added. ITL_BYPASS
bypasses the ENA_OPEN and ENA_CLOSE states.
Internal improvement.
Added inputs TRIP and SYNC_OK. Renamed input
ITL_BYPASS to SYNC_ITL_BYP. Added outputs
CL_REQ and OP_REQ. Outputs OPENPOS and
CLOSEPOS are forced to "FALSE" in case status is
Faulty (11).
Change
Maximum and default values changed to 60 s and 10
s respectively for
changed to 30 s for
Outputs OPENPOS and CLOSEPOS are forced to
"FALSE" in case status is Faulty (11).
Change
Maximum and default values changed to 60 s and 10
s respectively for
changed to 30 s for
Outputs OPENPOS and CLOSEPOS are forced to
"FALSE" in case status is Faulty (11).
IEC 61850
IEC 60617
identification
identification
DCSXSWI
I<->O DC
ESSXSWI
I<->O ES
Section 9
Control functions
Event delay settings. Default value
Operation timeout setting.
Event delay settings. Default value
Operation timeout setting.
ANSI/IEEE C37.2
device number
52-TOC, 29DS
29GS
971