Monitored Data - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 6
Differential protection
Name
Values (Range)
ZSCurrSubtrW1
Disabled
Enabled
ZSCurrSubtrW2
Disabled
Enabled
ZSCurrSubtrW3
Disabled
Enabled
6.1.2.5
6.1.3
90
Unit
Step
-
-
-
-
-
-

Monitored data

Table 28:
T3WPDIF (87T) Monitored data
Name
Type
IDMAG_A
REAL
IDMAG_B
REAL
IDMAG_C
REAL
IBIAS
REAL
IDMAG_NS
REAL
Operation principle
The task of the power transformer differential protection is to determine whether a fault
is within the protected zone, or outside of the protected zone. The protected zone is limited
by the position of current transformers (see figure 31), and in principle can include more
objects than just a transformer. If the fault is found to be internal, the faulty power
transformer must be quickly disconnected from the system.
The main CTs are normally supposed to be Wye connected and can be grounded in any
direction (that is, either "ToObject" or "FromObject"). Internally the IED will always
measure the currents on all sides of the power transformer with the same reference
direction towards the power transformer windings as shown in figure 31.
Default
Description
Enabled
Enable zero sequence subtraction for W1 side,
Off/On
Enabled
Enable zero sequence subtraction for W2 side,
Off/On
Enabled
Enable zero sequence subtraction for W3 side,
Off/On
Values (Range)
Unit
-
A
-
A
-
A
-
A
-
A
1MRK 502 048-UUS A
Description
Magnitude of fundamental
frequency differential current,
phase A
Magnitude of fundamental
frequency differential current,
phase B
Magnitude of fundamental
frequency differential current,
phase C
Magnitude of the bias current,
which is common to all phases
Magnitude of the negative
sequence differential current
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

650 seriesReg650 ansi

Table of Contents