Operation Principle - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.5.7.4
615 series ANSI
Technical Manual
protection 27 by allowing the grid operators to define its own Low-Voltage Ride-Through
(LVRT) curve for generators, as defined by local or national grid codes. The LVRT curve
can be defined accurately according to the requirements by setting the appropriate time-
voltage coordinates.
The function contains a blocking functionality. 27RT can be blocked with the BLOCK
input. Blocking resets timers and outputs.

Operation principle

The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of 27RT is described using a module diagram. All modules in the diagram
are explained in the next sections.
V_A_AB
LVRT
V_B_BC
curve
V_C_CA
monitoring
V
1
BLOCK
GUID-4B9C3BE5-5E7E-4877-8AE7-05C142CDD6CF V1 EN
Figure 328:
Functional module diagram
LVRT curve monitoring
LVRT curve monitoring starts with detection of undervoltage. Undervoltage detection
depends on Voltage selection setting. All selectable options are based on fundamental
frequency components.
Function uses phase-to-ground voltages when Voltage selection is set to "Highest Ph-to-
E" or "Lowest Ph-to-E" and phase-to-phase voltages when Voltage selection is set to
"Highest Ph-to-Ph" or "Lowest Ph-to-Ph".
When the Voltage selection setting is set to "Highest Ph-to-E", "Lowest Ph-to-E",
"Highest Ph-to-Ph" or "Lowest Ph-to-Ph", the measured three-phase voltages are
compared phase-wise to the set Voltage pickup value. If the measured value is lower than
the set Voltage pickup value setting in number of phases equal to that set Num of pickup
phases, the PICKUP output is activated.
The setting options available for Num of pickup phases are "Exactly 1 of 3", "Exactly 2 of
3", and "Exactly 3 of 3", which are different from conventional setting options available
in other functions. For example, Num of pickup phases is set to "Exactly 2 of 3", any two
voltages should drop below Voltage pickup value within one cycle network for the
Protection functions
TRIP
PICKUP
Section 4
659