Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.4.7
398
Susceptance reverse
This setting should be set based on the value of the maximum ground-fault current
produced by the feeder (considering possible feeder topology changes) with a security
margin. This ensures that the admittance operating point stays inside the "Box"-
characteristics during outside fault. The recommended security margin should not be
lower than 1.5.
Susceptance reverse: - (10 A * 1.5)/ (15 kV/sqrt(3)) = -1.73 mS
Conductance reverse
This setting is used to complete the non-directional characteristics by closing the "Box"-
characteristic. In order to keep the shape of the characteristic reasonable and to allow
sufficient margin for the admittance operating point during outside fault, it is
recommended to use the same value as for setting Susceptance reverse.
Conductance reverse = -1.73 mS
5
Bo ( mS )
4
3
2
1
0
‐1
Backward fault:
‐2
Yo ≈  ‐ j*1.15mS
‐3
‐4
‐5
0
‐5
‐4
‐3
‐2
‐1
1
GUID-1E9D7C77-63A6-40BF-AF9D-60CF77EA8940 V1 EN
Figure 191:
Admittances of the example

Signals

Table 379:
21YN Input signals
Name
Type
IG
SIGNAL
VG
SIGNAL
BLOCK
BOOLEAN
RELEASE
BOOLEAN
5
4
3
2
1
0
Go ( mS )
‐1
‐2
Forward fault, 
Y o ≈ 1.73+j*Bo mS
‐3
‐4
‐5
‐5
2
3
4
5
Default
Description
0
Residual current
0
Residual voltage
0=False
Block signal for activating the blocking mode
0=False
External trigger to release neutral admittance protection
1MAC059074-MB A
Bo ( mS )
TRIP
+0.1  m S
‐ 1.73 mS
‐ 1.73 mS
+0.35  m S
TRIP
‐4
‐3
‐2
‐1
0
1
2
615 series ANSI
Technical Manual
TRIP
Go ( mS )
TRIP
3
4
5