Generic control point (16 pcs) SPC

Identification

Function description
Generic control point (16 pcs)

Function block

SPC
BLOCK
Q1
IN1
Q2
IN2
Q3
IN3
Q4
IN4
Q5
IN5
Q6
IN6
Q7
IN7
Q8
IN8
Q9
IN9
Q10
IN10
Q11
IN11
Q12
IN12
Q13
IN13
Q14
IN14
Q15
IN15
Q16
IN16
GUID-0AA1476A-9C7C-418A-B104-580BC573B53D V1 EN
Figure 97:
Function block

Functionality

The generic control points function SPC contains 16 independent control points. SPC
offers the capability to activate its outputs through a local or remote control. The local
control request can be issued through the buttons in the single-line diagram or via inputs
and the remote control request through communication. The rising edge of the input signal
is interpreted as a control request, and the output operation is triggered. When remote
control requests are used, the control points behave as persistent.
The Loc Rem restriction setting is used for enabling or disabling the restriction for SPC to
follow the R/L button state. If Loc Rem restriction is "True", as it is by default, the local
or remote control operations are accepted according to the R/L button state.
Each of the 16 generic control point outputs has the Operation mode, Pulse length and
Description setting. If Operation mode is "Toggle", the output state is toggled for every
control request received. If Operation mode is "Pulsed", the output pulse of a preset
duration (the Pulse length setting) is generated for every control request received. The
IEC 61850
IEC 60617
identification
identification
SPCGAPC
SPC
Section 3
Basic functions
ANSI/
IEEEidentification
SPC