Function Block - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
8.1.12.2
8.1.12.3
8.1.12.4
Table 844:
SP,SE Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Power unit Mult
3=k
6=M
Energy unit Mult
3=k
6=M
Active power Dir
1=Forward
2=Reverse
Reactive power Dir
1=Forward
2=Reverse
615 series ANSI
Technical Manual

Function block

GUID-C6D692B2-FEA1-4450-A108-09C229A9CC0C V2 EN
Figure 477:
Function block
Signals
Table 843:
SP,SE Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
V_A
SIGNAL
V_B
SIGNAL
V_C
SIGNAL
RSTACM
BOOLEAN
Settings
Unit
Step
Measurement functions
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Phase A voltage
0
Phase B voltage
0
Phase C voltage
0=False
Reset of accumulated energy reading
Default
Description
1=enable
Operation Disable / Enable
3=k
Unit multiplier for presentation of the power
related values
3=k
Unit multiplier for presentation of the energy
related values
1=Forward
Direction of active power flow: forward, reverse
1=Forward
Direction of reactive power flow: forward,
reverse
Section 8
931

Advertisement

Table of Contents
loading

Table of Contents