Signals; Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 3
Basic functions
3.14.3.4
3.14.3.5
Table 65:
ULTVTR Non group settings (Basic)
Parameter
Values (Range)
Primary voltage
0.100...440.000
Secondary voltage
60...210
VT connection
1=Wye
2=Delta
3=VAB
4=VA
Table continues on next page
132
secondary circuit. The MINCB_OPEN signal sets the FUSEF_U output signal to block all
the voltage-related functions when MCB is in the open state.
The WARNING output in the receiver is activated if the synchronization accuracy of the
sender or the receiver is worse than 4 μs. The output is held on for 10 seconds after the
synchronization accuracy returns within limits. If the protection relay supports frequency
adaptivity and it is enabled, the WARNING output is also activated when the adaptivity is
not ready.
The WARNING output is always internally active whenever the ALARM output is active.
The receiver activates the WARNING and ALARM outputs if any of the quality bits, except
for the derived bit, is activated. When the receiver is in the test mode, it accepts SMV
frames with test bit without activating the WARNING and ALARM outputs.

Signals

Table 63:
ULTVTR Input signals
Name
Type
UL1
INT32-UL1
UL2
INT32-UL2
UL3
INT32-UL3
MINCB_OPEN
BOOLEAN
Table 64:
ULTVTR Output signals
Name
Type
ALARM
BOOLEAN
WARNING
BOOLEAN

Settings

Unit
Step
kV
0.001
V
1
Default
Description
0
IEC 61850-9-2 phase 1 voltage
0
IEC 61850-9-2 phase 2 voltage
0
IEC 61850-9-2 phase 3 voltage
0=False
Active when external MCB opens protected voltage
circuit
Description
Alarm
Warning
Default
Description
20.000
Primary rated voltage
100
Secondary rated voltage
2=Delta
Voltage transducer measurement connection
1MAC059074-MB A
615 series ANSI
Technical Manual