Settings; Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.4.7
Table 269:
49F Group settings (Basic)
Parameter
Values (Range)
Env temperature set
-50...100
Current reference
0.05...4.00
Temperature raise
0.0...200.0
Time constant
60...60000
Maximum temperature
20.0...200.0
Alarm value
20.0...150.0
Reclose temperature
20.0...150.0
Table 270:
49F Group settings (Advanced)
Parameter
Values (Range)
Current multiplier
1...5
Table 271:
49F Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 272:
49F Non group settings (Advanced)
Parameter
Values (Range)
Initial temperature
-50.0...100.0
4.1.4.8
274

Settings

Unit
Step
°C
1
xIn
0.01
°C
0.1
s
1
°C
0.1
°C
0.1
°C
0.1
Unit
Step
1
Unit
Step
Unit
Step
°C
0.1

Monitored data

Table 273:
49F Monitored data
Name
Type
TEMP
FLOAT32
TEMP_RL
FLOAT32
T_TRIP
INT32
Table continues on next page
Default
Description
40
Ambient temperature used when AmbiSens is
set to Off
1.00
The load current leading to Temperature raise
temperature
75.0
End temperature rise above ambient
2700
Time constant of the line in seconds.
90.0
Temperature level for trip
80.0
Temperature level for pickup (alarm)
70.0
Temperature for reset of block reclose after trip
Default
Description
1
Current multiplier when function is used for
parallel lines
Default
Description
1=enable
Operation Disable / Enable
Default
Description
0.0
Temperature raise above ambient temperature
at startup
Values (Range)
Unit
-100.0...9999.9
°C
0.00...99.99
0...60000
s
1MAC059074-MB A
Description
The calculated temperature of
the protected object
The calculated temperature of
the protected object relative to
the trip level
Estimated time to trip
615 series ANSI
Technical Manual