Section 4
Protection functions
4.6.1.7
Table 590:
81 Group settings (Basic)
Parameter
Values (Range)
Trip mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
Pickup value Freq>
0.9000...1.2000
Pickup value Freq<
0.8000...1.1000
Pickup value df/dt
-0.2000...0.2000
Trip Tm Freq
80...200000
Trip Tm df/dt
120...200000
Table 591:
81 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 592:
81 Non group settings (Advanced)
Parameter
Values (Range)
Reset delay Tm Freq
0...60000
Reset delay Tm df/dt
0...60000
4.6.1.8
684

Settings

Unit
Step
xFn
0.0001
xFn
0.0001
xFn /s
0.0025
ms
10
ms
10
Unit
Step
Unit
Step
ms
1
ms
1
Monitored data
Table 593:
81 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
ST_DUR_OFRQ
FLOAT32
ST_DUR_UFRQ
FLOAT32
ST_DUR_FRG
FLOAT32
81
Enum
Default
Description
1=Freq<
Frequency protection trip mode selection
1.0500
Frequency pickup value overfrequency
0.9500
Frequency pickup value underfrequency
0.0100
Frequency pickup value rate of change
200
Trip delay time for frequency
400
Trip delay time for frequency rate of change
Default
Description
1=enable
Operation Disable / Enable
Default
Description
0
Reset delay time for frequency
0
Reset delay time for rate of change
Values (Range)
Unit
0.00...100.00
%
0.00...100.00
%
0.00...100.00
%
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC059074-MB A
Description
Pickup duration
Pickup duration
Pickup duration
Pickup duration
Status
615 series ANSI
Technical Manual