Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.8.7
Table 303:
37 Group settings (Basic)
Parameter
Values (Range)
Current block value
0.00...0.50
Pickup value
0.01...1.00
Trip delay time
50...200000
Table 304:
37 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Operation mode
1=Three Phase
2=Single Phase
Table 305:
37 Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
296
Table 302:
37 Output signals
Name
Type
TRIP
BOOLEAN
TRIP_A
BOOLEAN
TRIP_B
BOOLEAN
TRIP_C
BOOLEAN
PICKUP
BOOLEAN
PICKUP_A
BOOLEAN
PICKUP_B
BOOLEAN
PICKUP_C
BOOLEAN

Settings

Unit
Step
xIn
0.01
xIn
0.01
ms
10
Unit
Step
Unit
Step
ms
1
Description
Trip
Trip phase A
Trip phase B
Trip phase C
Pickup
Pickup phase A
Pickup phase B
Pickup phase C
Default
Description
0.10
Low current setting to block internally
0.50
Current setting to pickup
2000
Trip delay time
Default
Description
1=enable
Operation Disable / Enable
1=Three Phase
Number of phases needed to pickup
Default
Description
20
Reset delay time
1MAC059074-MB A
615 series ANSI
Technical Manual