the first time delay is selected; for the second attempt, the second time delay and so on. For
the fourth and fifth attempts, the time delays are the same.
Time delay settings for the DEL_INIT_2 signal
Str 2 delay shot 1
Str 2 delay shot 2
Str 2 delay shot 3
Str 2 delay shot 4
Time delay settings for the DEL_INIT_3 signal
Str 3 delay shot 1
Str 3 delay shot 2
Str 3 delay shot 3
Str 3 delay shot 4
Time delay settings for the DEL_INIT_4 signal
Str 4 delay shot 1
Str 4 delay shot 2
Str 4 delay shot 3
Str 4 delay shot 4
Normally, only two or three reclosing attempts are made. The third and fourth attempts are
used to provide the so-called fast final trip to lockout.
GUID-36912067-F77E-457B-87D8-637CE0FA73A6 V1 EN
Figure 506:
Autoreclosing configuration example