Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
5.1.7
Table 671:
INR Group settings (Basic)
Parameter
Values (Range)
Pickup value
5...100
Trip delay time
20...60000
Table 672:
INR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 673:
INR Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
5.1.8
615 series ANSI
Technical Manual
Table 670:
INR Output signals
Name
Type
BLK2H
BOOLEAN

Settings

Unit
Step
%
1
ms
1
Unit
Step
Unit
Step
ms
1
Monitored data
Table 674:
INR Monitored data
Name
Type
INR
Enum
Protection related functions
Description
Second harmonic based block
Default
Description
20
Ratio of the 2. to the 1. harmonic leading to
restraint
20
Trip delay time
Default
Description
1=enable
Operation Disable / Enable
Default
Description
20
Reset delay time
Values (Range)
Unit
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 5
Description
Status
771

Advertisement

Table of Contents
loading

Table of Contents