Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 8
Measurement functions
8.1.11.4
Table 838:
P,E Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Power unit Mult
3=Kilo
6=Mega
Energy unit Mult
3=Kilo
6=Mega
Active power Dir
1=Forward
2=Reverse
Reactive power Dir
1=Forward
2=Reverse
Table 839:
P,E Non group settings (Advanced)
Parameter
Values (Range)
Forward Wh Initial
0...999999999
Reverse Wh Initial
0...999999999
Forward VArh Initial
0...999999999
Reverse VArh Initial
0...999999999
8.1.11.5
928

Settings

Unit
Step
Unit
Step
1
1
1
1
Monitored data
Table 840:
P,E Monitored data
Name
Type
S-kVA
FLOAT32
P-kW
FLOAT32
Q-kVAr
FLOAT32
PF
FLOAT32
RSTACM
BOOLEAN
S-kVA
FLOAT32
S_DB
FLOAT32
S_DMD
FLOAT32
Table continues on next page
Default
Description
1=enable
Operation Disable / Enable
3=Kilo
Unit multiplier for presentation of the power
related values
3=Kilo
Unit multiplier for presentation of the energy
related values
1=Forward
Direction of active power flow: Forward,
Reverse
1=Forward
Direction of reactive power flow: Forward,
Reverse
Default
Description
0
Preset Initial value for forward active energy
0
Preset Initial value for reverse active energy
0
Preset Initial value for forward reactive energy
0
Preset Initial value for reverse reactive energy
Values (Range)
Unit
-999999.9...9999
kVA
99.9
-999999.9...9999
kW
99.9
-999999.9...9999
kVAr
99.9
-1.00...1.00
0=False
1=True
-999999.9...9999
kVA
99.9
-999999.9...9999
kVA
99.9
-999999.9...9999
kVA
99.9
1MAC059074-MB A
Description
Total Apparent Power
Total Active Power
Total Reactive Power
Average Power factor
Reset of accumulated energy
reading
Total Apparent Power
Apparent power, magnitude of
reported value
Demand value of apparent
power
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents