Signals; Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.3.6
4.2.3.7
Table 372:
67NIEF Group settings (Basic)
Parameter
Values (Range)
Directional mode
1=Non-directional
2=Forward
3=Reverse
Trip delay time
40...1200000
Voltage pickup value
0.05...0.50
368
VA
VB
VC
GUID-80AEDA11-131C-473D-B6F7-5EFDA102A11B V1 EN
Figure 173:
Example of ground-fault transients, including discharge and charge
transient components, when a permanent fault occurs in a 20 kV network
in phase C

Signals

Table 370:
67NIEF Input signals
Name
Type
IG
SIGNAL
VG
SIGNAL
BLOCK
BOOLEAN
Table 371:
67NIEF Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLK_EF
BOOLEAN

Settings

Unit
Step
ms
10
xUn
0.01
Default
Description
0
Residual current
0
Residual voltage
0=False
Block signal for activating the blocking mode
Description
Trip
Pickup
Block signal for EF to indicate opposite direction peaks
Default
Description
2=Forward
Directional mode, Non-directional / Forward /
Reverse
500
Trip delay time
0.20
Voltage pickup value for transient EF
1MAC059074-MB A
615 series ANSI
Technical Manual