Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Table 419:
67YN Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Operation mode
1=Intermittent EF
3=General EF
4=Alarming EF
Table 420:
67YN Non group settings (Advanced)
Parameter
Values (Range)
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
Vg or V0
1=Measured VG
2=Calculated V0
Peak counter limit
2...20
Pickup delay time
30...60000
Reset delay time
0...60000
Pol reversal
0=False
1=True
4.2.8.8
615 series ANSI
Technical Manual
Unit
Step
Unit
Step
1
ms
1
ms
1

Monitored data

Table 421:
67YN Monitored data
Name
Type
PICKUP_DUR
FLOAT32
FAULT_DIR
Enum
DIRECTION
Enum
ANGLE
FLOAT32
67YN
Enum
Default
Description
1=enable
Operation Disable / Enable
3=General EF
Operation criteria
Default
Description
1=Measured IG
Measured IG or calculated I0
1=Measured VG
Selection for used Uo signal
2
Peak counter limit for restriking EF
30
Pickup delay time
500
Reset delay time
0=False
Rotate polarizing quantity
Values (Range)
Unit
0.00...100.00
%
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
3=both
-180.00...180.00
deg
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
Ratio of pickup time / trip time
Detected fault direction
Direction information
Angle between operating
angle and characteristic angle
Status
459

Advertisement

Table of Contents
loading