Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.7.1.7
Table 598:
78 Group settings (Basic)
Parameter
Values (Range)
Oos operate mode
1=Way in
2=Way out
3=Adaptive
Forward reach
0.00...6000.00
Reverse reach
0.00...6000.00
Inner blinder R
1.00...6000.00
Outer blinder R
1.01...10000.00
Impedance angle
10.0...90.0
Swing time
20...300000
Table 599:
78 Group settings (Advanced)
Parameter
Values (Range)
Zone 1 reach
1...100
Max number slips
1...10
Max Num slips Zn2
1...20
Max Num slips Zn3
1...20
Trip delay time
20...60000
Trip dropout time
20...60000
V dip time
500...5000
Zone 2 enable
1=Yes
0=No
Zone 3 enable
1=Yes
0=No
694
Table 597:
78 Output signals
Name
Type
TRIP
BOOLEAN
SWING_TRIP
BOOLEAN
SWING
BOOLEAN
OSB
BOOLEAN
OSB_Z2
BOOLEAN

Settings

Unit
Step
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
deg
0.1
ms
10
Unit
Step
%
1
1
1
1
ms
10
ms
10
ms
10
Description
Out of step trip on zone 1 or zone 2
Out of step trip on zone 3
Swing condition detected
Out of step block for zone 1
Out of step block for zone 2
Default
Description
2=Way out
Operate mode for tripping when out of step
condition is detected
1000.00
Forward reach of mho circle
100.00
Reverse reach of mho circle
150.00
Resistance value if inner blinder at R axis
400.00
Resistance value of outer blinder at R axis
90.0
Angle of mho circle and blinders with respect to
R axis
500
Time between blinders for swing to be detected
Default
Description
70
Percent of Mho forward reach indicating the
end of zone 1 and the beginning of zone 2
1
Number of pole slips before operating zone 1
1
Number of pole slips before operating zone 2
1
Number of pole slips before operating zone 3
300
Delay after OOS trip detected
100
Time trip output remains active
2000
Maximum allowable time for voltage to dip
0=No
Enable zone 2 feature
0=No
Enable zone 3 feature
1MAC059074-MB A
615 series ANSI
Technical Manual

Advertisement

Table of Contents