1MAC059074-MB A
Parameter
Values (Range)
Amplitude corr. A
0.9000...1.1000
Amplitude corr. B
0.9000...1.1000
Amplitude corr. C
0.9000...1.1000
Division ratio
1000...20000
Voltage input type
1=Voltage trafo
3=CVD sensor
Angle Corr A
-20.0000...20.0000
Angle Corr B
-20.0000...20.0000
Angle Corr C
-20.0000...20.0000
3.14.3.6
3.14.4
3.14.4.1
3.14.4.2
615 series ANSI
Technical Manual
Unit
Step
0.0001
0.0001
0.0001
1
deg
0.0001
deg
0.0001
deg
0.0001

Monitored data

Monitored data is available in three locations.
Monitoring/I/O status/Analog inputs
Monitoring/IED status/SMV traffic
Monitoring/IED status/SMV accuracy

RESTVTR function block

Function block

RESTVTR
VG
ALARM
WARNING
GUID-9C7DCCB2-018C-4DB3-9F70-30E2B411FD6F V1 EN
Figure 45:
Function block

Functionality

The RESTVTR function is used in the receiver application to perform the supervision for
the sampled values of analog residual voltage and to connect the received analog residual
voltage input to the application. Synchronization accuracy, sampled value frame transfer
delays and missing frames are being supervised.
Default
Description
1.0000
Phase A Voltage phasor magnitude correction
of an external voltage transformer
1.0000
Phase B Voltage phasor magnitude correction
of an external voltage transformer
1.0000
Phase C Voltage phasor magnitude correction
of an external voltage transformer
10000
Voltage sensor division ratio
1=Voltage trafo
Type of the voltage input
0.0000
Phase A Voltage phasor angle correction of an
external voltage transformer
0.0000
Phase B Voltage phasor angle correction of an
external voltage transformer
0.0000
Phase C Voltage phasor angle correction of an
external voltage transformer
Section 3
Basic functions
133