Section 4
Protection functions
Table 223:
50P Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 224:
50P Non group settings (Advanced)
Parameter
Values (Range)
Minimum trip time
20...60000
Reset delay time
0...60000
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Table 225:
50P-3 Group settings (Basic)
Parameter
Values (Range)
Pickup value
1.00...40.00
Pickup value mult
0.8...10.0
Trip delay time
20...200000
Table 226:
50P-3 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
228
Unit
Step
Default
1=enable
1=1 out of 3
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
Unit
Step
Default
ms
1
20
ms
1
20
2=DFT
Unit
Step
Default
xIn
0.01
1.00
0.1
1.0
ms
10
20
Unit
Step
Default
1=enable
1=1 out of 3
1MAC059074-MB A
Description
Operation Disable / Enable
Number of phases required for trip activation
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum trip time for IDMT curves
Reset delay time
Selects used measurement mode
Description
Pickup value
Multiplier for scaling the pickup value
Trip delay time
Description
Operation Disable / Enable
Number of phases required for trip activation
Technical Manual
615 series ANSI