Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Parameter
Values (Range)
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 264:
51V Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Control mode
1=Voltage control
2=Input control
3=Voltage and
input Ctl
4=No Volt
dependency
Minimum trip time
40...60000
Reset delay time
0...60000
4.1.3.8
615 series ANSI
Technical Manual
Unit
Step
1
1
1
1
Unit
Step
ms
1
ms
1

Monitored data

Table 265:
51V Monitored data
Name
Type
PICKUP_DUR
FLOAT32
EFF_ST_VAL_A
FLOAT32
EFF_ST_VAL_B
FLOAT32
EFF_ST_VAL_C
FLOAT32
51V
Enum
Default
Description
0.1217
Parameter B for customer programmable
curve
2.00
Parameter C for customer programmable
curve
29.10
Parameter D for customer programmable
curve
1.0
Parameter E for customer programmable
curve
Default
Description
2=DFT
Selects used measurement mode
1=Voltage control
Type of control
40
Minimum trip time for IDMT curves
20
Reset delay time
Values (Range)
Unit
0.00...100.00
%
0.00...50.00
xIn
0.00...50.00
xIn
0.00...50.00
xIn
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
Ratio of pickup time / trip time
Effective pickup value for
phase A
Effective pickup value for
phase B
Effective pickup value for
phase C
Status
267