Warnings

In case of a warning, the protection relay continues to operate except for those protection
functions possibly affected by the fault, and the green Normal LED remains lit as during
normal operation.
Warnings are indicated with the text Warning additionally provided with the name of the
warning, a numeric code and the date and time on the LHMI. The warning indication
message can be manually cleared.
If a warning appears, record the name and code so that it can be provided
to ABB customer service.
Table 24:
Warning indications and codes
Warning indication
Warning code
Warning
Watchdog reset
Warning
Power down det.
Warning
IEC61850 error
Warning
Modbus error
Warning
DNP3 error
Warning
Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning
Logic error
Warning
SMT logic error
Warning
GOOSE input error
ACT error
Warning
GOOSE Rx. error
Table continues on next page
Additional information
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has dropped
too low.
20
Error when building the IEC 61850 data
model.
21
Error in the Modbus communication.
22
Error in the DNP3 communication.
24
Error in the Data set(s).
25
Error in the Report control block(s).
26
Error in the GOOSE control block(s).
27
Error in the SCL configuration file or the file
is missing.
28
Too many connections in the
configuration.
29
Error in the SMT connections.
30
Error in the GOOSE connections.
31
Error in the ACT connections.
32
Error in the GOOSE message receiving.
Section 3