Application - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 10
Power quality measurement functions
10.1.5
1034
I_A
Distortion
I_B
measure-
ment
I_C
BLOCK
GUID-E5EC5FFE-7679-445B-B327-A8B1759D90C4 V1 EN
Figure 526:
Functional module diagram
Distortion measurement
The distortion measurement module measures harmonics up to the 11th harmonic. The
total demand distortion TDD is calculated from the measured harmonic components with
the formula
N
2
I
k
k
2
=
TDD
=
I
max_
demand
GUID-9F532219-6991-4F61-8DB6-0D6A0AA9AC29 V1 EN
I
th
k
harmonic component
k
I
The maximum demand current measured by IA, IB, IC
max_demand
If IA, IB, IC are not available in the configuration or the measured maximum demand
current is less than the Initial Dmd current setting, Initial Dmd current is used for
I
.
max_demand
Demand calculation
The demand value for TDD is calculated separately for each phase. If any of the calculated
total demand distortion values is above the set alarm limit TDD alarm limit, the ALARM
output is activated.
The demand calculation window is set with the Demand interval setting. It has seven
window lengths from "1 minute" to "180 minutes". The window type can be set with the
Demand window setting. The available options are "Sliding" and "Non-sliding".
The activation of the BLOCK input blocks the ALARM output.

Application

In standards, the power quality is defined through the characteristics of the supply voltage.
Transients, short-duration and long-duration voltage variations, unbalance and waveform
distortions are the key characteristics describing power quality. Power quality is,
Demand
ALARM
calculation
1MAC059074-MB A
(Equation 171)
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents