Delayed Initiation Lines - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
9.4.6.4
615 series ANSI
Technical Manual
A071274-ANSI V1 EN
Figure 523:
Three shots with three initiation lines
If the sequence is initiated from the INIT_1 line, that is, the overcurrent protection high
stage, the sequence is one shot long. If the sequence is initiated from the INIT_2 or
INIT_3 lines, the sequence is two shots long.
Table 906:
Settings for configuration example 2
Setting name
Shot number CBB1
Init signals CBB1
First reclose time
Shot number CBB2
Init signals CBB2
Second reclose time
Shot number CBB3
Init signals CBB3
Third reclose time

Delayed initiation lines

The autoreclose function consists of six individual autoreclose initiation lines
INIT_1...INIT 6 and three delayed initiation lines:
DEL_INIT_2
DEL_INIT_3
DEL_INIT_4
DEL_INIT_2 and INIT_2 are connected together with an OR-gate, as are inputs 3 and
4. Inputs 1, 5 and 6 do not have any delayed input. From the autoreclosing point of view,
it does not matter whether INIT_x or DEL_INIT_x line is used for shot initiation or
blocking.
Control functions
Setting value
1
1 (line 1)
0.0s (an example)
1
6 (lines 2 and 3 = 2+4 = 6)
0.2s (an example)
2
6 (lines 2 and 3 = 2+4 = 6)
10.0s