Section 3
Basic functions
Parameter
Values (Range)
Operation mode
0=Pulsed
1=Toggle
-1=Off
Pulse length
10...3600000
Description
Operation mode
0=Pulsed
1=Toggle
-1=Off
Pulse length
10...3600000
Description
3.17.12
3.17.12.1
3.17.12.2
3.17.12.3
196
Unit
Step
ms
10
ms
10
Generic up-down counter CTR
Identification
Function description
Generic up-down counter
Function block
GUID-222CC574-D72D-4426-876C-526D7C264C1E V1 EN
Figure 99:
Function block
Functionality
The multipurpose generic up-down counter function CTR counts up or down for each
positive edge of the corresponding inputs. The counter value output can be reset to zero or
preset to some other value if required.
The function provides up-count and down-count status outputs, which specify the relation
of the counter value to a loaded preset value and to zero respectively.
Default
Description
-1=Off
Operation mode for generic control point
1000
Pulse length for pulsed operation mode
SPCGAPC1
Generic control point description
Output 15
-1=Off
Operation mode for generic control point
1000
Pulse length for pulsed operation mode
SPCGAPC1
Generic control point description
Output 16
IEC 61850
IEC 60617
identification
identification
UDFCNT
UDCNT
1MAC059074-MB A
ANSI/IEEE C37.2
device number
CTR
615 series ANSI
Technical Manual